Fault mask, Sync mask, Traverse mask – Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 104: Logic mask, Local mask, Alarm mask

5–38
Programming
[Fault Mask]
This parameter controls which adapters can reset a
fault.
Parameter Number
100
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Sync Mask]
This parameter controls and chooses which
adapters can select the Sync function.
Parameter Number
101
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Traverse Mask]
This parameter controls and chooses which
adapters can select the Traverse function.
Parameter Number
190
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Logic Mask]
Determines which adapters can control the drive. If
the bit for an adapter is set to “0,” the adapter will
have no control functions except for stop. In addi-
tion, the adapter can be removed from the drive
while power is applied without causing a serial fault.
Parameter Number
92
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Local Mask]
This parameter controls which adapters are allowed
to take exclusive control of drive logic commands
(except stop). Exclusive “local” control can only be
taken while the drive is stopped.
Parameter Number
93
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Alarm Mask]
Controls which alarm conditions will
activate the alarm contact (refer to
Chapter 2 – TB2) and set the alarm
bit (bit 6) in [Drive Status].
With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number
206
Parameter Type
Read and Write
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor Stalled
Ground Warning
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Unused
Unused
Voltage Check
Heatsink Temp
Auxiliary Input
4-20 mA Loss
Overcurrent
Masks