Chapter

2

Installation/Wiring

Chapter 2 provides the information you need to properly mount and
wire the 1336 PLUS Drive. Since most start-up difficulties are the
result of incorrect wiring, every precaution must be taken to assure
that the wiring is done as instructed. All items must be read and
understood before the actual installation begins.

!

ATTENTION: The following information is merely
a guide for proper installation. The Allen-Bradley
Company cannot assume responsibility for the
compliance or the noncompliance to any code,
national, local or otherwise for the proper installation
of this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if
codes are ignored during installation.

Minimum Mounting Requirements for Proper Heat Dissipation
(Dimensions shown are between drives or other devices)

JOG

ESC

SEL

101.6 mm

(4.0 in.)

JOG

ESC

SEL

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

UP

NOTE: F Frame drives require 152.4 mm (6.0 in.) on the sides and/or back for proper air flow.

Mounting