Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 105

5–39
Programming
This group of parameters contains binary information to display which group of adapters
are issuing control commands.
Owners
Each Owner Parameter contains a bit for each
adapter. The drive will set an adapter’s bit to “1”
when that adapter is issuing a logic command and
to “Zero” when no command is being issued.
With a Series A (version 3.0) or Series B HIM, a
Status description (bit ENUM) is displayed on line
1.
TB3
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Not Used
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Owners Display
[Stop Owner]
This parameter displays which adapters are
presently issuing a valid stop command.
Parameter Number
102
Parameter Type
Read Only
Units
Display Drive
“0” 0
Stop Input Not Present
“1” 1
Stop Input Present
[Direction Owner]
This parameter displays which adapter currently has
exclusive control of direction changes.
Parameter Number
103
Parameter Type
Read Only
Units
Display Drive
“0” 0
Non-Owner
“1” 1
Current Owner
[Start Owner]
This parameter displays which adapters are
presently issuing a valid start command.
Parameter Number
104
Parameter Type
Read Only
Units
Display Drive
“0” 0
Start Input Not Present
“1” 1
Start Input Present
[Jog Owner]
This parameter displays which adapters are
presently issuing a valid jog command.
Parameter Number
105
Parameter Type
Read Only
Units
Display Drive
“0” 0
Jog Input Not Present
“1” 1
Jog Input Present
[Reference Owner]
This parameter displays which adapter currently has
the exclusive control of the selection of the
command frequency source.
Parameter Number
106
Parameter Type
Read Only
Units
Display Drive
“0” 0
Non-Owner
“1” 1
Current Owner
[Accel Owner]
This parameter displays which adapter has
exclusive control of selecting [Accel Time 1] or
[Accel Time 2].
Parameter Number
107
Parameter Type
Read Only
Units
Display Drive
“0” 0
Non-Owner
“1” 1
Current Owner