Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 88
5–22
Programming
[S Curve Time]
This creates an adjustable s curve ramp. If S Curve
Time is < the programmed accel/decel time, the
actual ramp will be the sum of the two. If S Curve
Time is
≥
the programmed accel/decel times, a fixed
S curve will be created whose time is double the
programmed accel/decel time.
Parameter Number
56
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Second / Seconds x 10
Factory Default
0.0 Sec
Minimum Value
0.0 Sec
Maximum Value
3000.0 Sec
[Language]
This parameter selects between English and the
alternate language (not currently available) for the
HIM display.
Parameter Number
47
Parameter Type
Read and Write
Factory Default
“English”
Units
Display Drive
“English” 0
“Alternate” 1
[Speed Control]
This parameter selects the type of speed modulation
active in the drive.
This parameter cannot be changed while the drive is
running.
Important: If encoder feedback closed loop speed
regulation is required, “Encoder Fdbk” must be
selected.
Parameter Number
77
Parameter Type
Read and Write
Factory Default
“No Control”
Units
Display Drive
“No Control” 0
Frequency regulation
“Slip Comp” 1
Slip compensation
“Speed Droop” 2
Negative slip compensation
“PLL” 3
Phase lock loop
“Encoder Fdbk” 4
Encoder feedback–closed loop
“Droop + Reg” 5
Enc. fdbk.–closed loop w/ active droop
“P Jump” 6
Traverse function
[Flying Start En]
This value enables the flying start function and
chooses the method to be used. The drive will first
search from the direction it was last running.
Parameter Number
155
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
“Speed Search” 1
Freq. sweep –see [FStart For./Rev.]
“Use Encoder” 2
Requires feedback encoder
“Track Volts” 3
Read back EMF from sync. p.m.
motor
ATTENTION: The “Speed Search” selection should not be
used with synchronous or permanent magnet motors. Motors
may be demagnetized during braking.
!
[FStart Forward]
This value sets the frequency at which the forward
speed search begins. If this value exceeds
[Maximum Freq], speed search will begin at
[Maximum Freq]. Forward search ends at zero Hertz
or when motor speed is found.
Parameter Number
156
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz
Factory Default
60 Hz
Minimum Value
0 Hz
Maximum Value
400 Hz
Feature Select