Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 28
2–20
Installation/Wiring
The available combinations are shown in Figure 2.5. Programming
the [Input Mode] parameter to one of the Input Mode numbers listed,
will select that combination of input functions.
Important:
If a Control Interface Option is not installed, the [Input
Mode] parameter must be set to 1 (default) and jumpers
must be installed as shown in Figure 2.7. If the drive
was shipped from the factory without the option, these
jumpers will have been installed.
Important:
The [Input Mode] parameter can be changed at any
time, but the change will not affect drive operation until
power to the drive has been removed and bus voltage
has decayed completely. When changing the [Input
Mode] parameter, it is important to note that the
functions of the TB3 inputs will change when power is
reapplied to the drive.
The programming options of the Control Interface Option allow the
user to select an input combination to meet the needs of a specific
installation. Appropriate selection of a combination may be done by
using Figure 2.5. First determine the type of start/stop/direction
control desired. Then select the remaining control functions
available. Record the selected mode number below.
Selected Mode Number:
Figure 2.4 provides the terminal designations for TB3. The
maximum and minimum wire size accepted by TB3 is 2.1 and 0.30
mm
2
(14 and 22 AWG). Recommended torque for all terminals is
0.90-1.13 N-m (8-10 lb.-in.). See Figure 2.6 for TB3 interconnection
information. Use Copper wire only.
Figure 2.4
TB3 Terminal Designations
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Input 1
Input 2 (Stop)
Common
Input 3
Input 4
Input 5
Common
Input 6
Input 7
Input 8
Common
Enable
Encoder B
Encoder NOT A
Encoder NOT B
Encoder A
+12V
(200mA max.)
Encoder Common
Included on L4E, L5E & L6E Only