Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 108
5–42
Programming
This group of parameters contains the parameters used to scale, in “User Units”, any drive
parameter for display on the HIM. Two scaled parameter values can be simultaneously
displayed when Process Mode is selected.
Process
Display
[Process 1 Par]
This parameter should be set to the number of the
parameter whose scaled value will be displayed on
Line 1 of the HIM Display Panel.
The maximum process value that can be displayed
is 99,999.99. If this value is exceeded, a character
string of asterisks (****) will appear on the display.
Parameter Number
127
Parameter Type
Read and Write
Display Units / Drive Units
Parameter # / Parameter #
Factory Default
1
[Process 1 Scale]
This value sets the scaling multiplier for
[Process 1 Par]. The displayed value will be:
[Process 1 Par] actual value
x [Process 1 Scale] value
Displayed Value
Parameter Number
128
Parameter Type
Read and Write
Display Units / Drive Units
Numeric / Scale x 100
Factory Default
+1.00
Minimum Value
–327.68
Maximum Value
+ 327.67
[Process 1 Txt 1-8]
Sets the “User Units” description for the value
determined by [Process 1 Par] and [Process 1 Scale].
This 8 character description will be shown on line 1 of
the display. Refer to the Character Map in Appendix A.
Parameter Number(s)
129-136
Parameter Type
Read and Write
Display Units / Drive Units
ASCII Code / ASCII Code
Factory Default
“Volts ”
[Process 2 Par]
This parameter should be set to the number of the
parameter whose scaled value will be displayed on
Line 2 of the HIM Display Panel.
The maximum process value that can be displayed
is 99,999.99. If this value is exceeded, a character
string of asterisks (****) will appear on the display.
Parameter Number
180
Parameter Type
Read and Write
Display Units / Drive Units
Parameter # / Parameter #
Factory Default
54
[Process 2 Scale]
This value sets the scaling multiplier for
[Process 2 Par]. The displayed value will be:
[Process 2 Par] actual value
x [Process 2 Scale] value
Displayed Value
Parameter Number
181
Parameter Type
Read and Write
Display Units / Drive Units
Numeric / Scale x 100
Factory Default
+1.00
Minimum Value
–327.68
Maximum Value
+ 327.67
[Process 2 Txt 1-8]
Sets the “User Units” description for the value
determined by [Process 2 Par] and [Process 2 Scale].
This 8 character description will be shown on line 2 of
the display. Refer to the Character Map in Appendix A.
Parameter Number(s)
182-189
Parameter Type
Read and Write
Display Units / Drive Units
ASCII Code / ASCII Code
Factory Default
“Amps ”