beautypg.com

Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 47

background image

3–7

Human Interface Module

Program and Display Modes

or

or

or

1. The Display and Program modes allow

access to the parameters for viewing or
programming.

A. From the Status Display, press Enter

(or any key). “Choose Mode” will be
shown.

B. Press the Increment (or Decrement)

key to show “Program” (or “Display”).

C. Press Enter.

D. Press the Increment (or Decrement) key

until the desired group is displayed.

E. Press Enter.

F. Press the Increment (or Decrement)

key to scroll to the desired parameter.

Choose Mode
Display

Choose Mode
Program

Choose Group
Metering

Output Current
0.00 Amps

or

Bit ENUMs

With drive software versions above 2.00
and a Series A (software version 3.0) or
Series B HIM, bit ENUMs (16 character
text strings) will be displayed to aid
interpretation of bit parameters.

G. Select a bit parameter with the Incre-

ment (or Decrement) keys.

H. Press the SELect key to view the

ENUM of the first bit. Pressing this
key again will move the cursor to the
left one bit.

A blinking underline cursor will indi-
cate that you are in the Display mode or
that a Read Only parameter as been
accessed. A flashing character will
indicate that the value can be changed.

Individual bits of a Read/Write parame-
ter can be changed in the same manner.
Pressing the SELect key will move the
cursor (flashing character) one bit to the
left. That bit can then be be changed by
pressing the Increment/Decrement keys.
When the cursor is in the far right
position, pressing the Increment/Decre-
ment keys will increment or decrement
the entire value.

Masks
Logic Mask

TB3
X1111111