Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 94
94
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
Chapter 5
Using the I/O (Adapter mode only)
Creating Ladder Logic Using the RSLogix 5000 Generic Profile, All
Versions
Option Module Parameter Settings for ControlLogix Controller Example
These option module settings were used for the example ladder logic program in
this section.
Option Module Host Parameter
Value
Description
01 - [DL From Net 01]
370
Points to drive Par. 370 - [Stop Mode A]
02 - [DL From Net 02]
371
Points to drive Par. 371 - [Stop Mode B]
03 - [DL From Net 03]
535
Points to drive Par. 535 - [Accel Time 1]
04 - [DL From Net 04]
536
Points to drive Par. 536 - [Accel Time 2]
05 - [DL From Net 05]
537
Points to drive Par. 537 - [Decel Time 1]
06 - [DL From Net 06]
538
Points to drive Par. 538 - [Decel Time 2]
07 - [DL From Net 07]
539
Points to drive Par. 539 - [Jog Acc Dec Time]
08 - [DL From Net 08]
556
Points to drive Par. 556 - [Jog Speed 1]
09 - [DL From Net 09]
557
Points to drive Par. 557 - [Jog Speed 2]
10 - [DL From Net 10]
571
Points to drive Par. 571 - [Preset Speed 1]
11 - [DL From Net 11]
572
Points to drive Par. 572 - [Preset Speed 2]
12 - [DL From Net 12]
573
Points to drive Par. 573 - [Preset Speed 3]
13 - [DL From Net 13]
574
Points to drive Par. 574 - [Preset Speed 4]
14 - [DL From Net 14]
575
Points to drive Par. 575 - [Preset Speed 5]
15 - [DL From Net 15]
576
Points to drive Par. 576 - [Preset Speed 6]
16 - [DL From Net 16]
577
Points to drive Par. 577 - [Preset Speed 7]
17 - [DL To Net 01]
370
Points to drive Par. 370 - [Stop Mode A]
18 - [DL To Net 02]
371
Points to drive Par. 371 - [Stop Mode B]
19 - [DL To Net 03]
535
Points to drive Par. 535 - [Accel Time 1]
20 - [DL To Net 04]
536
Points to drive Par. 536 - [Accel Time 2]
21 - [DL To Net 05]
537
Points to drive Par. 537 - [Decel Time 1]
22 - [DL To Net 06]
538
Points to drive Par. 538 - [Decel Time 2]
23 - [DL To Net 07]
539
Points to drive Par. 539 - [Jog Acc Dec Time]
24 - [DL To Net 08]
556
Points to drive Par. 556 - [Jog Speed 1]
25 - [DL To Net 09]
557
Points to drive Par. 557 - [Jog Speed 2]
26 - [DL To Net 10]
571
Points to drive Par. 571 - [Preset Speed 1]
27 - [DL To Net 11]
572
Points to drive Par. 572 - [Preset Speed 2]
28 - [DL To Net 12]
573
Points to drive Par. 573 - [Preset Speed 3]
29 - [DL To Net 13]
574
Points to drive Par. 574 - [Preset Speed 4]
30 - [DL To Net 14]
575
Points to drive Par. 575 - [Preset Speed 5]
31 - [DL To Net 15]
576
Points to drive Par. 576 - [Preset Speed 6]
32 - [DL To Net 16]
577
Points to drive Par. 577 - [Preset Speed 7]
TIP
The Host [DL From Net xx] parameters are inputs into the drive that come
from controller outputs (for example, data to write to a drive parameter). The
Host [DL To Net xx] parameters are outputs from the drive that go to
controller inputs (for example, data to read a drive parameter).