Viewing the option module status using parameters, When operating in adapter mode, When operating in tap mode – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 51
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
51
Configuring the Option Module
Chapter 3
press the ESC
soft key to cancel.
9.
Reset the option module using
Device Parameter 25 - [Reset Module] or
by cycling power to the drive so that the restored parameters take effect.
Viewing the Option Module
Status Using Parameters
The following parameters provide information about the status of the option
module. You can view these parameters at any time.
When Operating in Adapter Mode
When Operating in Tap Mode
IMPORTANT
When performing a Set Defaults, the drive may detect a conflict and
then not allow this function to occur. If this happens, first resolve the
conflict and then repeat this Set Defaults procedure. Common reasons
for a conflict include the drive running or a controller in Run mode.
Option Module
Device Parameter
Description
03 - [DLs From Net Act]
The number of controller-to-drive Datalinks that are included in the network I/O
connection (controller outputs).
04 - [DLs To Net Act]
The number of drive-to-controller Datalinks that are included in the network I/O
connection (controller inputs).
06 - [Net Addr Src]
Displays the source from which the option module IP address is taken. The source is
determined by the option module Node Address switch settings shown in
, and
the value of Device Parameter 05 - [Net Addr Sel] which can be any of the following:
• “1” (Parameters)—uses address from Device Parameters 07…10 - [IP Addr Cfg x]
• “2” (BOOTP)
• “3” (DHCP)—the default
20 - [Net Rate Act 1]
The data rate used by the option module’s ENET1 network port.
22 - [Net Rate Act 2]
The data rate used by the option module’s ENET2 network port.
38 - [Fr Peer Status]
The status of the consumed peer I/O input connection.
Values: 0 = Off; 1 = Waiting; 2 = Running; 3 = Faulted
29 - [DLs Fr Peer Act]
The number of peer-to-drive Datalinks that the drive is expecting.
40 - [DLs To Peer Act]
The number of drive-to-peer Datalinks that the drive is expecting.
Option Module
Device Parameter
Description
06 - [Net Addr Src]
Displays the source from which the option module IP address is taken. The source is
determined by the option module Node Address switch settings shown in
, and
the value of Device Parameter 05 - [Net Addr Sel] which can be any of the following:
• “1” (Parameters)—uses address from Device Parameters 07…10 - [IP Addr Cfg x]
• “2” (BOOTP)
• “3” (DHCP)—the default
20 - [Net Rate Act 1]
The data rate used by the option module’s ENET1 network port.
22 - [Net Rate Act 2]
The data rate used by the option module’s ENET2 network port.
24 - [Net Rate Act 3]
The data rate used by the option module’s ENET3 (DEVICE) port.