About parameter numbers, How parameters are organized, Parameters for adapter mode operation – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 140: Device parameters—adapter mode
140
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
Appendix B
Option Module Parameters
About Parameter Numbers
Each parameter set is independently and consecutively numbered.
How Parameters Are
Organized
The
Device Parameters and Host Parameters are separately displayed in a
Numbered List
view order.
Parameters for Adapter
Mode Operation
This section contains lists of
Device parameters and Host parameters available
when the option module is operated in Adapter mode.
Device Parameters—Adapter Mode
Configuration Tool
Numbering Scheme
• HIM
• DriveExplorer
• DriveExecutive
The Device parameters and Host parameters begin with parameter 01. For example, Device
Parameter 01 - [Port Number] and Host Parameter 01 - [Net to Drv DL 01] are
parameter 01 as indicated by this manual.
• Explicit Messaging
See
, Using Explicit Messaging (Adapter mode only) and
, EtherNet/IP Objects (Adapter mode only) for details.
Parameter
No.
Name and Description
Details
01
[Operating Mode]
Displays the option module’s operating mode set with the
Operating Mode Jumper J4 (
).
Values:
0 = Adapter
1 = Tap
Type:
Read Only
02
[Port Number]
Displays the drive port into which the option module is installed.
Typically, this is Port 4, 5 or 6.
Minimum:
4
Maximum:
6
Type:
Read Only
03
[DLs From Net Act]
Displays the number of controller-to-drive Datalinks that the
drive is using based on the I/O connection opened by the
controller.
Minimum:
0
Maximum:
16
Type:
Read Only
04
[DLs To Net Act]
Displays the number of drive-to-controller Datalinks that the
controller is using based on the I/O connection opened by the
controller.
Minimum:
0
Maximum:
16
Type:
Read Only
05
[Net Addr Sel]
Selects the source from which the option module’s node address
is taken when the Node Address switches (
)
are not being used (that is, switches set to any value other than
001…254 or 888).
Default:
3 = DHCP
Values:
1 = Parameters
2 = BOOTP
3 = DHCP
Type:
Read/Write
Reset Required:
Yes
06
[Net Addr Src]
Displays the source from which the option module’s node address
is taken.
Values:
0 = Switches
1 = Parameters
2 = BOOTP
3 = DHCP
Type:
Read Only