beautypg.com

Descriptor attributes – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual

Page 180

background image

180

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

Appendix C

EtherNet/IP Objects (Adapter mode only)

Descriptor Attributes

Bit

Name

Description

0

Data Type (Bit 1)

Right bit is least significant bit (0).
000 = USINT used as an array of Boolean
001 = UINT used as an array of Boolean
010 = USINT (8-bit integer)
011 = UINT (16-bit integer)
100 = UDINT (32-bit integer)
101 = TCHAR ((8-bit (not Unicode) or 16-bits (Unicode))
110 = REAL (32-bit floating point value)
111 = Use bits 16, 17, 18

1

Data Type (Bit 2)

2

Data Type (Bit 3)

3

Sign Type

0 = unsigned
1 = signed

4

Hidden

0 = visible
1 = hidden

5

Not a Link Sink

0 = May be the sink end of a link
1 = May not be the sink end of a link

6

Not Recallable

0 = Recallable from NVS
1 = Not Recallable from NVS

7

ENUM

0 = No ENUM text
1 = ENUM text

8

Writable

0 = Read only
1 = Read/write

9

Not Writable When Enabled

0 = Writable when enabled (for example, drive running)
1 = Not writable when enabled

10

Instance

0 = Parameter value is not a Reference to another parameter
1 = Parameter value refers to another parameter

11

Uses Bit ENUM Mask

This parameter instance supports the Bit ENUM Mask attribute. For more information, see the definition of the attribute.

12

Decimal Place (Bit 0)

Number of digits to the right of the decimal point.
0000 = 0
1111 = 15

13

Decimal Place (Bit 1)

14

Decimal Place (Bit 2)

15

Decimal Place (Bit 3)

16

Extended Data Type (Bit 4)

Bit 16 is the least significant bit.
000 = Reserved
001 = UDINT used as an array of Boolean
010 = Reserved
011 = Reserved
100 = Reserved
101 = Reserved
110 = Reserved
111 = Reserved

17

Extended Data Type (Bit 5)

18

Extended Data Type (Bit 6)

19

Parameter Exists

Used to mark parameters that are not available to network tools.

20

Not Used

Reserved

21

Formula Links

Indicates the Formula Data is derived from other parameters.

22

Access Level (Bit 1)

A 3-bit field used to control access to parameter data.

23

Access Level (Bit 2)

24

Access Level (Bit 3)

25

Writable ENUM

ENUM text: 0 = Read Only, 1 = Read/Write

26

Not a Link Source

0 = May be the source end of a link
1 = May not be the source end of a link

27

Enhanced Bit ENUM

Parameter supports enhanced bit ENUMs.

28

Enhanced ENUM

Parameter supports enhanced ENUMs.

29

Uses DPI Limits Object

Parameter uses the DPI Limits Object.
Intelligent offline tools make use of the Limits Object to select limits and units.

30

Extended Descriptor

Parameter uses Extended Descriptor bits, which can be obtained by reading the DPI Extended Descriptor attribute for this parameter.

31

Always Upload/Download

Parameter shall always be included in uploads and downloads.