Setting web page access – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 48
48
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
Chapter 3
Configuring the Option Module
Setting Web Page Access
By using a web browser to access the IP address set for the option module, you
can view the option module web pages for information about the module, the
drive and other DPI devices connected to the drive, such as HIMs or converters.
By default, the option module web pages are disabled. To enable the option
module web pages, set
Device Parameter 26 - [Web Enable] to “1” (Enabled).
For more details on the option module web pages, see
In Adapter mode, the option module can be configured to automatically send e-
mail messages to desired addresses when selected drive faults occur and/or are
cleared, and/or when the option module takes a communication or idle fault
action.
Bit 0 of
Device Parameter 27 - [Web Features] is used to protect the configured
settings for e-mail messaging. By default, settings are not protected and the user
can make changes. To protect the configured settings, set the value of E-mail Cfg
Bit 0 to “0” (Disabled). You can unprotect the configuration by changing Bit 0
back to “1” (Enabled). E-mail messaging will always remain active regardless of
whether or not its settings are protected—unless e-mail messaging was
never
configured. For more information about configuring option module e-mail
messaging or to stop e-mail messages, see
Notification Web Page on page 130
.
Bit 0 is the right-most bit. In the example above, it equals “1” (Enabled).
Changes to this parameter take effect immediately. A reset is not required.
IMPORTANT
Depending on its selected operating mode (Adapter or Tap), the option module
provides a unique set of web pages with different information.
Value
Description
0
Disabled (Default)
1
Enabled
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit Web Enable
Disabled
0
0 << 1
Bit
Description
0
E-mail Cfg (Default = 1 = Enabled)
1…15
Not Used
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit Web Features
xxxx xxxx xxxx xxx1
E-mail Cfg