Using option module parameters, Using option, Using – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 36: Using option module
36
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
Chapter 3
Configuring the Option Module
Using Option Module Parameters
By default, the option module is configured to use a DHCP server as the source
for the IP address, subnet mask, and gateway address for the option module. To
use option module parameters instead, you must first change the source for the
node address to “Parameters” and then set the associated option module
parameters as described in the following subsections.
Changing the Source for the Node Address
1.
Verify that the Node Address switches (
) are set to any
value other than 001…254 or 888. The default setting is 999.
2.
Set the value of
Device Parameter 05 - [Net Addr Sel] to “1” (Parameters).
3.
Reset the option module; see
Resetting the Option Module on page 49
.
4.
Perform the steps in the following subsections to set the IP address, subnet
mask, and gateway address using the option module parameters.
Setting the IP Address
1.
Verify that
Device Parameter 05 - [Net Addr Sel] is set to “1”
(Parameters).
2.
Set the value of
Device Parameters 07 - [IP Addr Cfg 1] through 10 - [IP
Addr Cfg 4]
to a unique IP address.
3.
Reset the option module; see
Resetting the Option Module on page 49
.
The NET A status indicator will be steady green or flashing green if the IP
address is correctly configured.
Value
Setting
1
Parameters
2
BOOTP
3
DHCP (default)