Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 16
16
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
Chapter 1
Getting Started
Tap Mode of Operation (only with PowerFlex 755 drives)
Step
Action
See
1
Review the safety precautions for the option module.
Throughout this manual
2
Verify that the PowerFlex drive is properly installed.
PowerFlex 750-Series AC Drive
Installation Instructions,
publication
3
Set the option module IP address.
a. When using the option module node address switches, set the IP
address now and proceed with step 4. When using a DHCP server,
BOOTP server, or option module parameters to set the IP address,
first perform step 3b and all of step 4. Then proceed with step 5.
b. Verify that the PowerFlex drive is not powered.
,
4
Install the option module.
a. Insert the option module in only PowerFlex 755 drive Port 4 or 5.
Use the captive crews to secure and ground the option module to
the drive.
b. Connect the option module to the network by using an Ethernet
cable.
Network Communication Option
Card Installation Instructions,
publication
,
5
Apply power to the option module.
a. The option module receives power from the drive. Verify that the
option module is installed correctly and then apply power to the
drive. The status indicators should be green. If they flash red, there
is a problem. See
b. Configure and verify key drive parameters.
,
6
Configure the option module for your application.
Set option module parameters for the following functions as required by
your application:
• IP address, subnet mask, and gateway address (only when not using
option module node address switches)
• Data rate
• Web enable and features
,
7
Set (or verify) the IP address for the embedded EtherNet/IP adapter in
the PowerFlex 755 drive.
PowerFlex 755 Drive Embedded
EtherNet/IP Adapter User Manual,
publication