Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 79
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
79
Configuring the I/O
Chapter 4
A configuration signature is generated.
2.
Access Safe Speed Monitor Module parameter 10 [Signature ID] and
record the configuration signature value stored in this parameter.
3.
Enter the current password for the Safe Speed Monitor Module into
parameter 1 [Password].
4.
Set Safe Speed Monitor Module parameter 5 [Lock State] to “1” (Lock).
These steps can be performed with a HIM, drive software configuration tool, or
via an HMI that can trigger explicit message writes from the controller program.
To meet SIL CL3, PLe, or Cat 4 requirements, the user must verify that the
correct configuration is locked in the Safe Speed Monitor Module. See the drive
and Safe Speed Monitor Module documentation for more information.
Monitoring ADC Progress
The time it takes for the ADC process to complete will vary from seconds to
several minutes depending on several factors:
•
The number of peripherals enabled for ADC.
•
If a configuration signature for the drive/peripheral indicates a
configuration download needs to be performed for the given port.
•
Whether Firmware Supervisor is enabled and needs to upgrade the drive
and/or any peripherals.
•
If a 20-750-S1 Safe Speed Monitor option module, which requires a
manual ‘step’ in its configuration process, is used.
•
If a DeviceLogix program (Port 14) is used.
With the Firmware Supervisor enabled, startup can take quite a long time. With
all firmware and parameters being updated, it takes approximately 45…55 minutes.
See the PowerFlex 750-Series AC Drive Programming Manual, publication
, for information about the drive status indicators. An operational drive in
a running Logix system will have the following status indicator states.
IMPORTANT
ADC can automatically reset the drive as part of the configuration process. This
is done because some parameters require a reset before they take effect. If a
drive is being replaced with an out-of-the-box drive, you will typically see at
least two resets during the ADC process—one for the parameters in the drive
(Port 0) and, for a PowerFlex 755 drive, one for the parameters in the
embedded EtherNet/IP adapter (Port 13).
Status
Indicator
Color
State
Description
STS
(Drive)
Green
Flashing
Drive ready but not running, and no faults are present.
Steady
Drive running, no faults are present.
NET A
Green
Steady
Option module is operating and has at least one CIP connection (I/O or explicit).
NET B
Green
Flashing
Option module is transmitting on the network.