Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 123
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
123
Troubleshooting
Chapter 7
Table 12 - Option Module Events
Code
Event Text
Description
Option Module Events
1
No Event
Text displayed in an empty event queue entry.
2
Device Power Up
Power was applied to the option module.
3
Device Reset
The option module was reset.
4
EEPROM CRC Error
The EEPROM checksum/CRC is incorrect, which limits option module functionality. Default parameter values must be loaded to clear this condition.
5
App Updated
The option module application firmware was updated.
6
Boot Updated
The option module boot firmware was updated.
7
Watchdog Timeout
The software watchdog detected a failure and reset the option module.
DPI Events
8
DPI Bus Off
A bus-off condition was detected on DPI.
9
DPI Ping Timeout
A ping message was not received on DPI within the specified time.
10
DPI Port Invalid
The option module was not connected to a valid port on a DPI product.
11
DPI Port Changed
The DPI port changed after startup.
12
DPI Host Reset
The drive sent a reset event message.
13
DPI Baud 125kbps
The option module detected that the drive was communicating at 125 Kbps.
14
DPI Baud 500kbps
The option module detected that the drive was communicating at 500 Kbps.
15
DPI Host Invalid
The option module was connected to an incompatible product.
16
DPI Dup Port
Another peripheral with the same port number is already in use.
17
DPI Type 0 Logon
The option module has logged in for Type 0 control.
18
DPI Type 0 Time
The option module has not received a Type 0 status message within the specified time.
19
DPI DL Logon
The option module has logged into a Datalink.
20
DPI DL Error
The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another peripheral.
21
DPI DL Time
The option module has not received a Datalink message within the specified time.
22
DPI Ctrl Disable
The option module has sent a “Soft Control Disable” command to the drive.
23
DPI Ctrl Enable
The option module has sent a “Soft Control Enable” command to the drive.
24
DPI Msg Timeout
A Client-Server message sent by the option module was not completed within 1 second.
25
DPI Manual Reset
The option module was reset by changing its Reset Module parameter.
SI Events
26
SI Online
The option module has logged into the Serial Interface Communication.
27
SI Logon Error
The option module failed to log into the Serial Interface.
28
SI Comm Fault
The Serial Interface Communication has faulted.
Network Events
29-30
Reserved
—
31
Net Dup Address
The option module uses the same address as another device on the network.
32
Net Comm Fault
The option module detected a communication fault on the network.
33
Net Sent Reset
The option module received a reset from the network.
34
Net IO Close
An I/O connection from the network to the option module was closed.
35
Net Idle Fault
The option module received “idle” packets from the network.
36
Net IO Open
An I/O connection from the network to the option module has been opened.