Table 1 – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 27
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
27
Installing the Option Module
Chapter 2
Table 1 - Adapter Mode – Drive and Option Module Start-Up Status Indications
After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see
.
Item
Name
Color
State
Description
Drive STS Indicator
➊
STS
(Status)
Green
Flashing
Drive ready but not running, and no faults are present.
Steady
Drive running, no faults are present.
Yellow
Flashing
When running, a type 2 (non-configurable) alarm condition exists –
drive continues to run. When stopped, a start inhibit condition exists
and the drive cannot be started (see drive parameter 933 - [Start
Inhibits]).
Steady
A type 1 (user configurable) alarm condition exists, but the drive
continues to run.
Red
Flashing
A major fault has occurred. Drive will stop. Drive cannot be started
until fault condition is cleared.
Steady
A non-resettable fault has occurred.
Red/
Yellow
Flashing
Alternately
A minor fault has occurred. Use drive parameter 950 - [Minor Flt
Config] to enable. If not enabled, acts like a major fault. When
running, the drive continues to run. System is brought to a stop under
system control. The fault must be cleared to continue.
Yellow/
Green
Flashing
Alternately
When running, a type 1 alarm exists.
Green/Red
Flashing
Alternately
Drive is updating.
Option Module Status Indicators—Adapter Mode
➋
PORT
Green
Flashing
Normal operation. The option module is establishing an I/O
connection to the drive. It will turn steady green or red.
Steady
Normal operation. The option module is properly connected and
communicating with the drive.
➌
MOD
Green
Flashing
Normal operation. The option module is operating but is not
transferring I/O data to a controller.
Steady
Normal operation. The option module is operating and transferring
I/O data to a controller.
➍
NET A
Unlit
Off
Normal operation. DHCP is enabled or a valid IP address is not set.
Green
Flashing
Normal operation. DHCP is disabled, the option module is properly
connected, has an IP address, and is connected to an EtherNet/IP
network—but does not have an I/O connection.
Steady
Normal operation. The option module is properly connected and
communicating on the network to a controller.
➎
NET B
Unlit
Off
Normal operation. The option module is properly connected, but is
idle.
Green
Flashing
Normal operation. The option module is properly connected, DHCP is
enabled, and the option module is transmitting on the network.