Configuring the Option Module
Chapter 3
7.
If a Logic Command is being sent, use
Device Parameter 30 - [Logic Src
Cfg]
to set the number of the Datalink that contains the Logic Command
within the range defined by
Device Parameter 28 - [DLs Fr Peer Cfg].
For example, if
Device Parameter 28 - [DLs Fr Peer Cfg] is set to receive
five Datalinks (Datalinks 12 through 16) and the first of those five
Datalinks (Datalink 12) contains the Logic Command, set
Device
Parameter 30 - [Logic Src Cfg]
to a value of “1.” Otherwise, set Parameter
30 to a value of “0.” For Logic Command bit definitions, see
or the drive documentation.
8.
If a Reference is being sent, use
Device Parameter 31 - [Ref Src Cfg] to set
the number of the Datalink that contains the Reference within the range
defined by
Device Parameter 28 - [DLs Fr Peer Cfg].
For example, if
Device Parameter 28 - [DLs Fr Peer Cfg] is set to receive
five Datalinks (Datalinks 12 through 16) and the second of those five
Datalinks (Datalink 13) contains the Reference, set
Device Parameter 31 -
[Ref Src Cfg]
to a value of “2.” Otherwise, set Parameter 31 to a value of
“0.”
9.
In each PowerFlex 750-Series slave drive, set drive parameter 308 -
[Direction Mode] to “0” (Unipolar) to be sure that it properly follows the
master drive’s speed reference and commanded direction.
10.
Resetting the Option Module on page 49
) so
that changes to
Device Parameter 28 - [DLs Fr Peer Cfg] take effect.
11.
Set
Device Parameter 37 - [Fr Peer Enable] to a value of “2” (Custom).
Value
Setting
0
Off (Default)
1
Cmd/Ref
2
Custom
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit Fr Peer Enable
Off
0
0 << 2