Table 2, For t – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 28
28
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
Chapter 2
Installing the Option Module
Table 2 - Tap Mode – PowerFlex 755 Drive and Option Module Start-Up Status Indications
After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see
Item
Name
Color
State
Description
Drive STS Indicator
➊
STS
(Status)
Green
Flashing
Drive ready but not running, and no faults are present.
Steady
Drive running, no faults are present.
Yellow
Flashing
When running, a type 2 (non-configurable) alarm condition exists –
drive continues to run. When stopped, a start inhibit condition exists
and the drive cannot be started (see drive parameter 933 - [Start
Inhibits]).
Steady
A type 1 (user configurable) alarm condition exists, but the drive
continues to run.
Red
Flashing
A major fault has occurred. Drive will stop. Drive cannot be started
until fault condition is cleared.
Steady
A non-resettable fault has occurred.
Red/
Yellow
Flashing
Alternately
A minor fault has occurred. Use drive parameter 950 - [Minor Flt
Config] to enable. If not enabled, acts like a major fault. When
running, the drive continues to run. System is brought to a stop under
system control. The fault must be cleared to continue.
Yellow/
Green
Flashing
Alternately
When running, a type 1 alarm exists.
Green/Red
Flashing
Alternately
Drive is updating.
Option Module Status Indicators—Tap Mode
➋
OK
Green
Flashing
Normal operation. The option module is establishing DPI
communication with the drive. It will turn steady green or red.
Steady
Normal operation. The option module has established DPI
communication with the drive.
➌
➍
➎
LINK 1
LINK 2
LINK 3
Unlit
Off
The option module is not properly connected to the network.
Green
Flashing
Normal operation. There is a 100 Mbps network link, with activity.
Steady
Normal operation. There is a 100 Mbps network link, no activity.
Yellow
Flashing
Normal operation. There is a 10 Mbps network link, with activity.
Steady
Normal operation. There is a 10 Mbps network link, no activity.