Configuring the daily tariff schedule – SATEC PM130 PLUS Manual User Manual
Page 93

Chapter 5 Configuring
T H E P M 1 3 0 P L U S
Configuring
B I L L I N G / T O U
PM130 PLUS Powermeter Series
93
Parameter
Options
Default
Description
Multiplier
0.001 to 100.000
1.000
The multiplication factor for the energy
source. Unchangeable for internal energy
sources.
Target
Reg#1- Reg#4
None
Defines the target billing register for the
energy source. It is set automatically.
Configuring the Daily Tariff Schedule
To configure your daily tariff schedule, select Energy/TOU from the
Meter Setup menu, and then click on the TOU Daily Profiles tab.
Figure 5-16: Energy/TOU Setup Dialog Box – TOU Daily Profiles Tab
The daily profile setup allows you to specify the daily tariff change points
with a 15-minute resolution for 4 seasons using 4 different daily schedules
for each season.
To configure your daily profiles:
1. Select the desired season and day
type.
2. Select the start time for each tariff change point and the
corresponding active tariff number.
3. Repeat the setup for all active profiles.
The first tariff change point is fixed at 00:00 hours, and the last tariff
change you specified will be in use until 00:00 hours on the next day.
NOTE
The billing daily profile log file is automatically configured for the number
of active tariffs you defined in the meter TOU daily profiles.