Factory preset data log files – SATEC PM130 PLUS Manual User Manual
Page 101

Chapter 5 Configuring
T H E P M 1 3 0 P L U S
Configuring
R E C O R D E R S
PM130 PLUS Powermeter Series
101
Factory Preset Data Log Files
Conventional Data Log #1
Data log #1 is factory preset for 15-min periodic recording of the standard
energy and demand quantities. You can freely change the list of recorded
parameters and the file update rate.
The default list of parameters is shown in the following table.
No.
Parameter
1
kWh import
2
kWh export
3
kW import sliding demand
4
V1 demand
5
V2 demand
6
V3 demand
Periodic recording data is triggered by Setpoint #1 that is linked to the
meter clock. To change the periodic rate at which data is recorded, change
the time interval for the MINUTE INTERVAL trigger in Setpoint #1 (see
Configuring Alarm/Control Setpoints
Billing/TOU Profile Data Log #16
Data log #16 is pre-configured for daily billing energy and maximum
demand recording for the last 90 days. It is automatically updated once a
day.