Using pas – SATEC PM130 PLUS Manual User Manual
Page 80

Chapter 5 Configuring
T H E P M 1 3 0 P L U S
General
M E T E R S E T U P
80
PM130 PLUS Powermeter Series
1. Press the ENTER button when the
middle window is highlighted.
You are returned to the upper window
and can select another analog output
or exit the menu.
2. Press ESC to exit the menu.
See Table 24 for the available analog output options.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the
Analog Outputs tab.
Figure 5-10: General Setup Dialog Box – Analog Outputs Tab
The available analog output options are described in Table 24.
Table 24: Analog Output Options
Display
Label
Option
Range
Description
-
AO type
0-1mA
±1mA
0-20mA
4-20mA
The analog output type. When connected to the
meter, shows the actual AO type received from
the device. When working off-line, select the
analog output option corresponding to your
analog module.
OutP
Output
parameter
See Appendix B Selects the measured parameter to be
transmitted through the analog output channel.
Lo
Zero scale
Defines the low engineering scale (in primary
units) for the analog output corresponding to a
lowest (zero) output current (0 or 4 mA)