Appendix g, Device diagnostic codes, Appendix g device diagnostic codes – SATEC PM130 PLUS Manual User Manual
Page 158
Appendix G Device Diagnostic
C O D E S
158
PM130 PLUS Powermeter Series
Appendix G Device Diagnostic Codes
Table 40: Device Diagnostic Codes
Diagnostic
Code
Diagnostic
Message
Description
Reason
2
dAtA
Memory/Data fault
Hardware failure
3
rSt
Hardware watchdog reset
Hardware failure
5
CPU
CPU exception
Hardware failure
6
runt
Run-time software error
Hardware failure
7
tout
Software watchdog
timeout
Hardware failure
8
PWr.UP
Power Down/Up
Normal power-up sequence
9
rStrt
Warm restart
External restart via
communications or by
firmware upgrade
10
ConF
Configuration reset
Corrupted setup data has
been replaced with the
default configuration
11
rtc
RTC fault
The clock time has been lost
13
Lo.bAt
Low battery (with a
battery backup unit)
Battery replacement is
required
15
EEPr
EEPROM fault
Hardware failure
in Chapter 3 for more information on the PM130
PLUS built-in diagnostics.