Voltage input connection, Current input connection, 690v inputs (standard) v – SATEC PM130 PLUS Manual User Manual
Page 24: Voltages 690v input (standard), 120v inputs (option u)

Chapter 2 Installation
Electrical
I N S T A L L A T I O N
24
PM130 PLUS Powermeter Series
Voltage Input connection
The equipment installation shall conform to the following
instructions:
a) a switch or circuit-breaker shall be included in the building
installation;
b) It shall be in close proximity to the equipment and within
easy reach of the OPERATOR;
c) It shall be marked as the disconnecting device for the
equipment.
Before installing, ensure that all incoming power sources
are shut OFF. Failure to observe this practice can result in
serious or even fatal injury and damage to equipment.
690V Inputs (Standard)
V
1
V
2
V
N
V
3
V
1
V
2
V
3
Voltages
690V Input (Standard)
690
690
690
400
400
400
690V inputs are usually used with direct connection. Use any of the seven
wiring configurations shown in Figures 2-8 through 2-15.
120V Inputs (Option U)
V
1
V
2
V
N
V
3
V
1
V
2
V
3
Voltages
120V Input (Option U)
120
120
120
120
120
120
120V inputs usually imply use of a potential transformer (PT). The PT
requires use of any of the four wiring configurations shown in Figures 2-7
through 2-10.
Current Input Connection
The PM130 does not have current terminals.
Using internal CT, the PM130 PLUS does not have current terminals
Using external CT (HACS – High Accuracy SATEC Current Sensor),
the PM130 PLUS provides current terminals
To connect to the external CT, pass the external CT wire through the
meter CT core, see Figure 2-8
for details and observe the arrow that
indicates the current direction.