Chapter 6 Device Control and
Upgrading
This section describes operations on the meter you can perform from the
front display or via PAS. To access device control options from PAS, you
should have your meter online.
6.1 Resetting Accumulators, Maximum Values and Files
Using the Front Display
Select the rst entry from the main menu. See
in Chapter 3 for information on configuring parameters via
the front display.
To reset the desired values:
1. Highlight the middle window by
pressing briefly the SELECT button.
2. Select a reset entry by scrolling through the list with the UP
and DOWN arrow buttons.
3. Press the SELECT button briefly to highlight the lower item.
4. Press and hold the ENTER button for 5 seconds.
5. Release the button.
The do entry is replaced with done
showing the operation is complete.
Table 31 shows the reset options available from the front display.
Table 31: Front Display Reset Options
Display Label
Description
EnrG
Clears all total energies
dnd
Clears all maximum demands
P.dnd
Clears power maximum demands
A.dnd
Clears ampere and volt maximum demands
Lo.Hi
Clears Min/Max log
Cnt
Clears all counters
Cnt1 – Cnt4
Clears counter #1-#4
diAG
Clears device diagnostics
Using PAS
Ensure that the On-line button on the PAS toolbar is checked, and then
select Reset from the Monitor menu.