General meter setup, Basic meter setup, 2 general meter setup basic meter setup – SATEC PM130 PLUS Manual User Manual
Page 71: Using the front display, Using pas
Chapter 5 Configuring
T H E P M 1 3 0 P L U S
General
M E T E R S E T U P
PM130 PLUS Powermeter Series
71
5.2 General Meter Setup
Basic Meter Setup
This section describes how to configure the PM130 PLUS for your
particular environment and application.
Before operating your meter, provide the device with basic information
about your electrical network.
Using the Front Display
Select the baSc entry from the main menu. See
in Chapter 3 for information on configuring parameters via
the front display.
See the table below for the Basic Setup options.
Using a shortcut to the Basic Setup menu:
From the Data Display, press and release the SELECT button to enter the
primary meter menu and then simultaneously press the SELECT and UP
buttons. You are directly moved to the CT setting entry.
The shortcut is not operational if the meter is password protected.
Using PAS
Select General Setup from the Meter Setup menu. See the table below
for the Basic Setup options.
Table 19: Basic Setup Options
Display
Label
Parameter
Options
Default
Description
Basic Configuration
ConF
Wiring Mode
4Ln3
The wiring connection of the device
Pt
PT Ratio
1.0-6500.0
1.0
The phase potential transformer’s
primary to secondary ratio
Pt.F
PT Ratio Multiplier
Ч1, Ч10
Ч1
PT Ratio multiplication factor. Used
in extra high voltage networks to
accommodate the PT ratio for
500 kV and higher networks.
Ct
CT Primary Current
1-50000 A
5 A
The primary rating of the phase
current transformer
Freq
Nominal Frequency
50,60,25,400 Hz 60 Hz
The nominal line frequency
LoAd
Maximum Demand
Load Current
0-50000 A
0
The maximum demand load
current (0 = CT primary current)
Demand Setup
d.P
Power block demand
period
E, EH
1, 2, 3, 5, 10, 15,
20, 30, 60 min,
E=external sync
15 min
The length of the demand period
for power demand calculations. If
the external synchronization is
selected, a pulse front on the
digital input DI1 denotes the start
of the demand interval.