Parameter data transfer
Lenze parameter sets
Parameter sets for 82XX controllers
l
83
EDSMF2133IB EN 5.0
8.1
Lenze parameter sets
(
Stop!
82XX / 8200 vector / Drive PLC and communication module:
ƒ
The cyclic writing of parameter data into the EEPROM is not permissible. It
may damage or destroy the EEPROM.
Only 8200 vector:
ƒ
After every mains switching, set code C0003 to the value "0" if you want to
change the parameter data cyclically.
8.1.1
Parameter sets for 82XX controllers
The 82XX controller has two parameter sets, the parameters of which can be directly
addressed.
Addressing
Addressing is effected by means of a code offset:
l
Offset 0 addresses parameter set 1 with the Lenze codes C0000 to C1999.
l
Offset "2000" addresses parameter set 2 with the Lenze codes C2000 to C3999.
If a parameter is only available once (see Operating Instructions for the controller), use code offset "0".
Example
Addressing of code C0011 (maximum field frequency) in different parameter sets:
l
C0011 in parameter set 1: Lenze code number = 11
l
C0011 in parameter set 2: Lenze code number = 2011
If a parameter is only available once (see Operating Instructions for the controller), use code offset "0".
)
Note!
ƒ
Automatic storage of the parameter data changed
ƒ
No automatic storage of process data