Process data transfer

Lenze device control

Process data signals for 82XX frequency inverters

7

l

51

EDSMF2133IB EN 5.0

AIF

C0046

.B15

.B13
.B14

.B12

.B0

.B1
.B2

.B3

.B4

...

...

...

.B8

.B9

.B10

.B11

QSP

CINH

TRIP-SET

TRIP-RESET

16 Bit

16 Bit

0

JOG/

C046

0 1 1

0 1 0 1

PAR

GSB

R/L

2141LON010

Fig. 7−3

Access to control word and frequency setpoint in 82XX (fixed assignment)

Special features

(

Stop!

ƒ

Only carry out a TRIP reset via the fieldbus!
The drive might start running for a short period if a fault is reset via
terminal 28 while the controller is being operated with fieldbus control
(C0001 = 3) and has assumed the device status "FAULT".

ƒ

If the setpoint and the direction of rotation are changed simultaneously via
the DRIVECOM speed setpoint, a speed change in the wrong direction of
rotation may occur for a short time.
For this reason always send a low rotation direction setpoint first, followed
by the new setpoint if the direction of rotation is changed.
This is because first the setpoint is sent to the controller as a unipolar value,
followed by the information on the change of the rotation direction.

The X controller is initialised after the "fault reset" command. During this time the
controller does not accept any other commands.