beautypg.com

4 profidrive status word, Profidrive status word, Process data transfer – Lenze EMF2133IB User Manual

Page 81

background image

Process data transfer

PROFIdrive control

PROFIdrive status word

7

l

81

EDSMF2133IB EN 5.0

7.3.4

PROFIdrive status word

Bit

Name

Meaning

0

Ready to start

Device status information
0 = Status lower than "READY TO START"
1 = Status at least "READY TO START"

1

Ready for
operation

Device status information
0 = Status lower than "READY FOR OPERATION"
1 = Status at least "READY FOR OPERATION"

2

Operation
enabled

Device status information
0 = Status lower than "OPERATION ENABLED"
1 = Status "OPERATION ENABLED"

3

Fault

Device status information
0 = No fault (TRIP)
1 = Fault (TRIP) occurred

4

OFF2

Information via command OFF2
0 = Command active
1 = Command not active

5

OFF3

Information via command OFF3
0 = Command active
1 = Command not active

6

Switch−on
inhibit

Device status information
0 = Status not "SWITCH−ON INHIBIT"
1 = Status "SWITCH−ON INHIBIT"

7

Warning

Collective warning
0 = no warning
1 = warning

8

Reserved

Always 1

9

Master
function
requested

82xx / 821x /
822x / 8200
vector

Bus access right, depending on Lenze parameter "Operating mode"
(C0001)
0 = C0001 <> 3
1 = C0001 = 3

93XX

1

10

Setpoint
reached

Status of the speed/frequency deviation
0 = HLG on <> HLG off
1 = RFG on = RFG off

11

Reserved

0

12

Manufacturer

82xx / 821x /
822x

Not used

8200 vector /
93XX

Mapping to bit C0150.B14

13

Manufacturer

82xx / 821x /
822x

Not used

8200 vector

Mapping to bit C0150.B15

93XX

Mapping to bit C0150.B3

14

Manufacturer

82xx / 821x /
822x

I

max

(current limit reached)

0 = Current limit not reached
1 = Current limit exceeded

8200 vector /
93XX

Mapping to bit C0150.B2

15

Manufacturer

82xx / 821x /
822x

Q min (f d < dQmin )
0 = Q min not active
1 = Q min active

8200 vector /
93XX

Mapping to bit C0150.B5