beautypg.com

4 technical data, 1 general data, Technical data – Lenze EMF2133IB User Manual

Page 16: General data, 4technical data

background image

Technical data

General data

4

l

16

EDSMF2133IB EN 5.0

4

Technical data

4.1

General data

Area

Values

Order designation

EMF2133IB

PNO ID number

2133

hex

Communication profile
(DIN 19245 Part 1 and Part 3)

l

PROFIBUS−DP−V0

l

PROFIBUS−DP−V1

Communication medium

RS485

Interface

9−pin Sub−D socket

Drive profile

l

DRIVECOM profile "drive technology 20" (can be switched off)

l

PROFIdrive profile (can be switched off, state machine and PROFIdrive
parameter data channel)

Network topology

l

without repeaters: Line

l

with repeaters: Line or tree

PROFIBUS nodes

Slave

Baud rate [kbps]

9.6 ... 12000 (automatic detection)

Process data words

1 ... 12 words
(16 bits/word)

DP user data length

1 ... 12 process data words +
4 parameter data words

Max. number of stations

l

Standard: 32 (= 1 bus segment)

l

with repeater: 125

Max. cable length per bus
segment

1200 m (depending on the baud rate and cable type used)

External DC voltage supply

V = +24 V DC ±10 %
I = 120 mA

,

Documentation for Lenze series of devices 8200 vector, 9300 and ECS

Here you can find the ambient conditions and the electromagnetic