Process data transfer

Lenze device control
Setpoint source selection

7

l

46

EDSMF2133IB EN 5.0

7.1

Lenze device control

7.1.1

Setpoint source selection

)

Note!

Note that the selection of the setpoint source must be set the same in all
parameter sets.

82XX / 8200 vector frequency inverters

For these controllers the setpoint source selection is determined under code C0001. An
evaluation of process data is only possible if code C0001 is set to "3" when the controller
is operated together with the communication module (selection: Process data channel of
a communication module). The process data channel which defines the frequency setpoint
(mapping to C0046) is the setpoint source and the control word (C0135).

In case of the 8200 vector, the assignment of the setpoint source to the corresponding
analog signal can be checked or changed in code C0412.

93XX controller

For operation via PROFIBUS, code C0005 must be set to the value "xxx3" (x = wildcard for
selected preconfiguration).

Example: C0005 = 1013: "Speed control" preconfiguration

ECSxS axis module

For operation via the PROFIBUS, code C3005 "Control mode" must be set:

ƒ

C3005 = 1003 (setpoint via AIF, speed−controlled)

ƒ

C3005 = 4003 (setpoint via AIF, torque−controlled)

Servo PLC 9300 / Drive PLC / ECSxA

Operation via the PROFIBUS requires that the system blocks AIF−IN1 ... 3, AIF−OUT1 ... 3
and, if available, the AIF management are part of the control configuration of the IEC61131
project.

ƒ

For cyclic process data telegrams to the drive , the AIF−IN1 ... 3 system blocks are
used. The control word (byte 1 and byte 2) contained in a process data telegram is
further processed via these system blocks in the standard device.

ƒ

For cyclic process data telegrams from the drive , the system blocks AIF−OUT1 ... 3 are
used. The status word (byte 1 and byte 2) contained in the process data telegram is
transmitted to the master via these system blocks .