Installing a Power Supply Module
38
Warning
When installing this equipment, always ensure that the frame
ground connection is installed first and disconnected last.
! 18
Figure 16 Connecting the Stripped Wire
e.
Connect the positive feed wire to the terminal block marked +
(positive).
f.
Connect the negative feed wire to the terminal block marked -
(negative).
Warning
Safety Hazard - Check to see if there are any exposed copper
strands coming from the installed wires. When this installation is
done correctly there should be no exposed copper wire strands
extending from the terminal block. Any exposed wiring can
conduct harmful levels of electricity to persons touching the wires.
! 19
g.
Secure the tray supply cable near the rack using multiple cable
ties (not provided). This will help minimize the chance of the
connections being disturbed by casual contact with the wiring.
It is recommended that you use at least four cable ties 10
centimeters (4 inches) apart with the first one located within 15
centimeters (6 inches) of the terminal block.