:SYSTem:CONFigure:PROTection:RECovery
Set
Query
Description
Sets or queries how the OHP, FAN, AC-FAIL, and
SD alarms are cleared.
Syntax
Return Syntax
:SYSTem:CONFigure:PROTection:RECovery
{SAFE|AUTO}
:SYSTem:CONFigure:PROTection:RECovery?
Parameter
SAFE
The output is not turned on automatically
when the cause of the alarm is fixed.
AUTO
The output is turned on automatically
when the cause of the alarm is fixed.
:SYSTem:CONFigure:MSLave
Set
Query
Description
Sets or queries the unit operation mode. This
setting is only applied after the unit has been reset.
Syntax
Query Syntax
:SYSTem:CONFigure:MSLave {
:SYSTem:CONFigure:MSLave?
Parameter/Return
0
Master/Local
1
Master/with 1 unit in Parallel (total:2 units)
2
Master/with 2 units in Parallel (total: 3 units)
3
Master/with 3 units in Parallel (total: 4 units)
4
Slave
:SYSTem:CONFigure:OUTPut:EXTernal
[:MODE]
Set
Query
Description
Sets the external logic as active high or active low.
This setting is only applied after the unit has been
reset.
Syntax
Query Syntax
:SYSTem:CONFigure:OUTPut:EXTernal[:MODE]
{
:SYSTem:CONFigure:OUTPut:EXTernal[:MODE]?