beautypg.com

Fairbanks FB2550 SERIES User Manual

Page 119

background image

Section 5: Input/ Output

07/2012

119

51254 Rev. 3

5.15.4. MODBUS (

30925

)

MODBUS PROTOCOL

was originally developed in 1978 to exchange

information between devices on the factory floor.

It developed into the standard for exchanging data and communication

MODULE

STATUS

– information between PLC systems.

– Modbus devices communicate over a Serial Network in a master/slave

(request/response) type relationship.

– Uses either the ASCII (American Standard Code for Information Interchange)

mode or the RTU (Remote Terminal Unit) mode.

In the

ASCII MODE

, two eight-bit bytes of data are sent as two ASCII characters.

– The primary advantage of ASCII mode is the flexibility of the timing sequence.

– Up to a one second interval can occur between character transmissions

without causing communication errors.

In the

RTU MODE

, data is sent as two four-bit, hexadecimal characters, providing

for higher throughput than in ASCII mode for the same baud rate.

– Modbus Plus communicates using a single twisted pair of wires in one

shielded cable (#18AWG).

– Modbus Plus does NOT provide power on the network.

Maximum of up to 32 Nodes, and up to 64 with a Repeater.

No.

DESCRIPTION

1

Communication LED

2

Device Status LED

3

Modbus Interface