5 technoforce metasys n2 comunication points – Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual

Page 71

background image

TECHNOFORCE Installation, Operation, and Maintenance

65

Appendix

Function Points # Point

Range/

Modbus Units

Code

Description

Value

Address

04

25

Speed %

0 to 100

30025

%

04

26

Lead Pump Number

1 to Pump # (in TechnoForce

User Setup Menu)

30026

04

27

Active Zone Number

1 to Zone # (in TechnoForce

User Setup Menu)

30027

7.5 TechnoForce Metasys N2 Comunication Points

NPT NPA Point Description

Range/Value

Units

BI

1

Pump #1 Failure

1 = Failure 0 = O.K.

BI

2

Pump #1 VFD Failure

1 = Failure 0 = O.K.

BI

3

Pump #1 Off Alarm

1 = Alarm 0 = O.K.

BI

4

Pump #2 Failure

1 = Failure 0 = O.K.

BI

5

Pump #2 VFD Failure

1 = Failure 0 = O.K.

BI

6

Pump #2 Off Alarm

1 = Alarm 0 = O.K.

BI

7

Pump #3 Failure

1 = Failure 0 = O.K.

BI

8

Pump #3 VFD Failure

1 = Failure 0 = O.K.

BI

9

Pump #3 Off Alarm

1 = Alarm 0 = O.K.

BI

10 Pump #4 Failure

1 = Failure 0 = O.K.

BI

11 Pump #4 VFD Failure

1 = Failure 0 = O.K.

BI

12 Pump #4 Off Alarm

1 = Alarm 0 = O.K.

BI

13 Pump #5 Failure

1 = Failure 0 = O.K.

BI

14 Pump #5 VFD Failure

1 = Failure 0 = O.K.

BI

15 Pump #5 Off Alarm

1 = Alarm 0 = O.K.

BI

16 Pump #6 Failure

1 = Failure 0 = O.K.

BI

17 Pump #6 VFD Failure

1 = Failure 0 = O.K.

BI

18 Pump #6 Off Alarm

1 = Alarm 0 = O.K.

BI

19 System Reset Required

1 = Yes 0 = No

BI

20 Pump #1 Enabled

1 = Enabled 0 = Disabled

BI

21 Pump #2 Enabled

1 = Enabled 0 = Disabled

BI

22 Pump #3 Enabled

1 = Enabled 0 = Disabled

BI

23 Pump #4 Enabled

1 = Enabled 0 = Disabled

BI

24 Pump #5 Enabled

1 = Enabled 0 = Disabled

BI

25 Pump #6 Enabled

1 = Enabled 0 = Disabled

BI

26 Pump #1 On/Off

1 = On 0 = Off

BI

27 Pump #2 On/Off

1 = On 0 = Off

BI

28 Pump #3 On/Off

1 = On 0 = Off

BI

29 Pump #4 On/Off

1 = On 0 = Off

BI

30 Pump #5 On/Off

1 = On 0 = Off

BI

31 Pump #6 On/Off

1 = On 0 = Off

BI

32 System Start/Stop

1 = Start 0 = Stop

BI

33 Analog Input #1 Failure

1 = Failure 0 = O.K.

BI

34 Analog Input #2 Failure

1 = Failure 0 = O.K.