5 technoforce metasys n2 comunication points – Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual
Page 71

TECHNOFORCE Installation, Operation, and Maintenance
65
Appendix
Function Points # Point
Range/
Modbus Units
Code
Description
Value
Address
04
25
Speed %
0 to 100
30025
%
04
26
Lead Pump Number
1 to Pump # (in TechnoForce
User Setup Menu)
30026
04
27
Active Zone Number
1 to Zone # (in TechnoForce
User Setup Menu)
30027
7.5 TechnoForce Metasys N2 Comunication Points
NPT NPA Point Description
Range/Value
Units
BI
1
Pump #1 Failure
1 = Failure 0 = O.K.
BI
2
Pump #1 VFD Failure
1 = Failure 0 = O.K.
BI
3
Pump #1 Off Alarm
1 = Alarm 0 = O.K.
BI
4
Pump #2 Failure
1 = Failure 0 = O.K.
BI
5
Pump #2 VFD Failure
1 = Failure 0 = O.K.
BI
6
Pump #2 Off Alarm
1 = Alarm 0 = O.K.
BI
7
Pump #3 Failure
1 = Failure 0 = O.K.
BI
8
Pump #3 VFD Failure
1 = Failure 0 = O.K.
BI
9
Pump #3 Off Alarm
1 = Alarm 0 = O.K.
BI
10 Pump #4 Failure
1 = Failure 0 = O.K.
BI
11 Pump #4 VFD Failure
1 = Failure 0 = O.K.
BI
12 Pump #4 Off Alarm
1 = Alarm 0 = O.K.
BI
13 Pump #5 Failure
1 = Failure 0 = O.K.
BI
14 Pump #5 VFD Failure
1 = Failure 0 = O.K.
BI
15 Pump #5 Off Alarm
1 = Alarm 0 = O.K.
BI
16 Pump #6 Failure
1 = Failure 0 = O.K.
BI
17 Pump #6 VFD Failure
1 = Failure 0 = O.K.
BI
18 Pump #6 Off Alarm
1 = Alarm 0 = O.K.
BI
19 System Reset Required
1 = Yes 0 = No
BI
20 Pump #1 Enabled
1 = Enabled 0 = Disabled
BI
21 Pump #2 Enabled
1 = Enabled 0 = Disabled
BI
22 Pump #3 Enabled
1 = Enabled 0 = Disabled
BI
23 Pump #4 Enabled
1 = Enabled 0 = Disabled
BI
24 Pump #5 Enabled
1 = Enabled 0 = Disabled
BI
25 Pump #6 Enabled
1 = Enabled 0 = Disabled
BI
26 Pump #1 On/Off
1 = On 0 = Off
BI
27 Pump #2 On/Off
1 = On 0 = Off
BI
28 Pump #3 On/Off
1 = On 0 = Off
BI
29 Pump #4 On/Off
1 = On 0 = Off
BI
30 Pump #5 On/Off
1 = On 0 = Off
BI
31 Pump #6 On/Off
1 = On 0 = Off
BI
32 System Start/Stop
1 = Start 0 = Stop
BI
33 Analog Input #1 Failure
1 = Failure 0 = O.K.
BI
34 Analog Input #2 Failure
1 = Failure 0 = O.K.