TECHNOFORCE Installation, Operation, and Maintenance
31
Installation
4.10.29 Test set up
Paths: Status Screens / Set up(3) / Test(4)
The
TEST menu screen gets displayed:
Test Selection: #
1=DI 4=AO 7=Disp
2=DO 5=LED 8=Comm
3=AI 6=Key 9=VFD Comm
Press the numeric key corresponding to the desired sub-menu, and then press the
ENTER key.
4.10.30 Digital input test
Paths: Status Screens / Set up(3) / Test(4) / DI(1)
The Digital Input Test screen is displayed below:
Digital Inputs
1
2
3
4
5
6
7
8
9
10
12
13
# # # # # # # # # # # #
Press Clear to Exit
The 0 below each corresponding input will change to a 1 upon receiving a 24VDC digital input on that channel.
Press
CLEAR key to exit the test.
4.10.31 Digital output test
Paths: Status Screens / Set up(3) / Test(4) / DO(2)
The Digital Output Test screen is displayed below:
Digital Outputs
1
2
# #
Enter DO# # (0=Exit)
Press the numeric key corresponding to the digital output for which the state is to be changed, and then press
ENTER to change it. Pressing ENTER multiple times will toggle between 0 and 1. A 1 indicates that the
corresponding relay is closed. When the relay is closed, the corresponding LED on the digital output module will
be lit. Press
0 and ENTER to exit the test.
Note: Any device connected to the relay will be energized.
4.10.32 Analog input test
Paths: Status Screens / Set up(3) / Test(4) / AI(3)
The Analog Input Test screen is displayed below:
Analog Inputs
1=###% 3 =###%
2=###% 4=###%
The signal received on the corresponding analog input channel will be indicated in percent next to each input.
4mA = 0%, and 20mA = 100%. Analog inputs 1-4 are 4-20mA inputs. Press
CLEAR key to exit the test.
4.10.33 Analog output test
Paths: Status Screens / Set up(3) / Test(4) / AO(4)
The Analog Output Test screen is displayed below:
Analog Output Test
AO1=###%
OK: $(Y/N)
The signal sent through the corresponding analog output channel will be indicated in percent next to each output.
4mA = 0%, and 20mA = 100%. Analog output is 4-20mA output. Press
CLEAR key to exit the test.