TECHNOFORCE Installation, Operation, and Maintenance

29

Installation

Friction Loss Compensation Menu Items (Continued)

Menu Item

Variable

Default Range Field

Value

Loss2 : ###

0 0-999

The max loss in PSI that will be compensated for two pumps.

This value will be used to adjust the setpoint when two pumps

are running. This value will get subtracted from the setpoint as

a fixed value when less than two pumps are running.

Loss3 : ###

0 0-999

The max loss in PSI that will be compensated for three pumps.

This value will be used to adjust the setpoint when three pumps

are running. This value will get subtracted from the setpoint

as a fixed value when less than three pumps are running.

Loss4 : ###

0 0-999

The max loss in PSI that will be compensated for four pumps.

This value will be used to adjust the setpoint when four pumps

are running. This value will get subtracted from the setpoint

as a fixed value when less than four pumps are running.

Loss5 : ###

0 0-999

The max loss in PSI that will be compensated for five pumps.

This value will be used to adjust the setpoint when five pumps

are running. This value will get subtracted from the setpoint

as a fixed value when less than five pumps are running.

Loss6 : ###

0 0-999

The max loss in PSI that will be compensated for six pumps.

This value will be used to adjust the setpoint when six pumps

are running. This value will get subtracted from the setpoint

as a fixed value when less than six pumps are running.

4.10.24 Save/load menu

Paths: Status Screens / Set up(3) / System(3) / SaveLoad(12)
The Save/Load menu has been displayed below:
Selection: # 0=Exit
1=Save to Flash
2=Load from Flash
3=Load Default
Use the appropriate numeric key to select the appropriate menu desired, press the

ENTER key. A detailed

description of each menu follows.

4.10.25 Save to flash

The Save To Flash screen is displayed below:
SAVE TO FLASH
Previously Saved Data
Will be overwritten!
PROCEED: $(Y/N)
Press

YES and ENTER to save all of the user setup to the flash memory. Saving to flash will overwrite any data

that was previously saved. Saving to flash memory will save all setup information to the Flash PROM chip within

the controller
A

load from flash will have to be performed to recover this saved data. See the following section.

Frict. Loss

Comp.