beautypg.com

Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual

Page 34

background image

TECHNOFORCE Installation, Operation, and Maintenance

28

Installation

Paths: Status Screens / Set up(3) / System(4) / Frict. Loss Comp. (11)
The Friction Loss Compensation screen has been displayed below:
Frict. Loss: ###

>

Auto: $

Enable: $

Log Stab Tmr: ###S
Log Reset: $

OK? $

Press the

YES/7 key to confirm the selection or Press next (►) key to go to the next screen. The display now

shows:

OK? $

Loss1 : ###

Loss4 : ###

Loss2 : ###
Loss3 : ###
Press the Y

ES/7 key to confirm the selection.

Figure 1

Note: “Setpoint” In figure 1 is the maximum control setpoint, will correspond to the controlling setpoint from

the SP1 value. Refer to section 5 for SP1 value selection.

Friction Loss Compensation Menu Items

Menu Item

Variable

Default Range Field

Value

Frict. Loss: ###

0 0-999

Total friction loss of the system in PSI. System Syzer tool from

the B&G website can be used to estimate friction loss.

Auto: $

N

Y/N

Select “Y” and enter to calculate Loss1 thru 6 value

automatically. Summation of Loss1 thru 6 will be equal to

Frict. Loss if calculated using this parameter. Value

of Loss1 to 6 can be also overwritten as required.

Enable: $

N

Y/N

Select “Y” to enable friction loss compensation.

Log Stab Tmr: ###S

30 0-255

Time in seconds for which new setpoint must stabilize to log.

Log Reset: $

N

Y/N

Select “Y” and enter to reset run time setpoint log.

Total: ####

N/A N/A

Displays the total of Loss1 to 6 (read only).

Loss1: ###

0 0-999

The max loss in PSI that will be compensated for one pump.

This value will be used to adjust the setpoint when one pump

is running.

Loss1

Loss2

Loss3

H

Q

Setpoint - (Loss1 + Loss2 + Loss3)

Setpoint - (Loss2 + Loss3)

Setpoint - (Loss3)

Setpoint

Frict. Loss

Comp.