Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual
Page 23

TECHNOFORCE Installation, Operation, and Maintenance
17
Installation
To set up each field, press the
NO/0 key and ENTER key. Modify the values as desired using the appropriate
keys. Modify the values as desired for pump 1.
Note: For example, to enter a value of 3.5 Amps, go to the amps field, press numerical key 3 and
press enter. Then press key 5 and enter.
To change the values for other pumps, press the
NEXT/( ) key. This is only applicable if the total numbers of
pumps selected in
TOTAL PUMPS: # field are more than 1.
Note:
All values will be copied to the next screen by pressing
NEXT/( ) key. They will only be copied the first time
the screens are visited. To edit the values, press the
NO/0 key and ENTER key. Modify the values as desired.
To confirm the modified values, press
YES/7 key and then press ENTER key.
The screen will go back to the
PUMP SET UP MENU display.
To change the values in
RESET PUMP TIME field, press the SETUP/3 key then press the ENTER key. The
following menu will get displayed:
RESET PUMP TIME?
P1: N
P2: N
P3: N
P4: N
P5: N
P6: N
OK $ (Y/N)
To reset the pump(s) run time, press
NO/0 key and ENTER.
By default,
N will be displayed next to the pump fields (P1: , P2: etc.) depending upon number of pumps
selected.
N corresponding to P1: field will start blinking. To reset the pump run time for pump 1, press the
YES/7 key and ENTER. Similarly modify the values for the rest of the pumps as applicable.
Note: This selection is only valid for the pumps selected. For example, if the number of pumps selected is 2, the
following screen will get displayed:
RESET PUMP TIME?
P1: N
P2: N
P3: N/A
P4: N/A P5: N/A P6: N/A
OK N (Y/N)
To confirm all the selections made, press
YES/7 key and then press ENTER key. The screen will go back to the
PUMP SET UP MENU display.
Pressing the
NO/0 key and then ENTER key at the PUMP SET UP screen will take the display back to the
MAIN SET UP screen.
4.10.2 System set up
Paths: Status Screens / Set up(3)
Press the
SETUP/3 key at the Main Set Up menu screen. Then press the ENTER key.
The first screen will get displayed as shown below:
< SELECTION: # >
1 = STAGE/DESTAGE
2 = VFD
3 = EXERCISE 0 = EXIT
Press the
NEXT/( ) key to go to the next screen. The display now shows:
< SELECTION: # >
4 = ALTERNATION 5=PID
6 = RESET TOTALS
7 = DATE, TIME 0 = EXIT
Press the
NEXT/( ) key to go to the next screen. The display now shows:
< SELECTION: # >
8 = PASSWORD 0 = EXIT
▲
▲
▲
▲