beautypg.com

Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual

Page 28

background image

TECHNOFORCE Installation, Operation, and Maintenance

22

4.10.9 Daily alternation

The Daily Alternation screen is displayed below:
Daily
Alt. Time: HH:MM
Enable: $ (Y/N)
OK? $(Y/N)
To edit the alternation time, press the

NO/0 key and ENTER key. Modify the values as desired.

Enter the Alternation Time in 24Hr format (range being 0:00-23:59) at which pumps will alternate daily. Press

YES/7 key to enable Daily alternation. Press the YES/7 key again to confirm the selection.

4.10.10 Weekly alternation

The Weekly Alternation screen is displayed below:
Alt. Day of week: #
1=Mon...7=Sun
Time HH:MM (0-23)
Enable: $(Y/N)
OK? $(Y/N)
To edit the displayed values, press the

NO/0 key and ENTER key. Modify the values as desired.

Enter the Alternation Day of Week (1= Monday…….7=Sunday) on which the pumps will be alternated.
Enter the Alternation Time in 24Hr format (range being 0:00-23:59).
Press YES/7 key to enable Monthly alternation. Press the YES/7 key again to confirm the selection.

4.10.11 Monthly alternation

The Monthly Alternation screen is displayed below:
Alt. Day of Month: #
(1-31)
Time HH:MM (0-23)
Enable: $(Y/N) OK? $(Y/N)
To edit the displayed values, press the

NO/0 key and ENTER key. Modify the values as desired.

Enter the Alternation Day of Month (1, 2, 3, 4….31 etc.) on which the pumps will be alternated.
Enter the Alternation Time in 24Hr format (range being 0:00-23:59).
Press

YES/7 key to enable Monthly alternation. Press the YES/7 key again to confirm the selection.

If 29,30 or 31 is entered as the day, the sequence will automatically alternate on the last day of the month.
Note:

In case Timed Auto Alt is in enabled state and Scheduled Auto Alt also gets enabled, Timed Auto Alt will get

disabled and a warning message “Timed Alteration will be disabled” will be displayed on the screen. Press

CLEAR key to go back to the ALTERNATION menu.

Installation