Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual
Page 28

TECHNOFORCE Installation, Operation, and Maintenance
22
4.10.9 Daily alternation
The Daily Alternation screen is displayed below:
Daily
Alt. Time: HH:MM
Enable: $ (Y/N)
OK? $(Y/N)
To edit the alternation time, press the
NO/0 key and ENTER key. Modify the values as desired.
Enter the Alternation Time in 24Hr format (range being 0:00-23:59) at which pumps will alternate daily. Press
YES/7 key to enable Daily alternation. Press the YES/7 key again to confirm the selection.
4.10.10 Weekly alternation
The Weekly Alternation screen is displayed below:
Alt. Day of week: #
1=Mon...7=Sun
Time HH:MM (0-23)
Enable: $(Y/N)
OK? $(Y/N)
To edit the displayed values, press the
NO/0 key and ENTER key. Modify the values as desired.
Enter the Alternation Day of Week (1= Monday…….7=Sunday) on which the pumps will be alternated.
Enter the Alternation Time in 24Hr format (range being 0:00-23:59).
Press YES/7 key to enable Monthly alternation. Press the YES/7 key again to confirm the selection.
4.10.11 Monthly alternation
The Monthly Alternation screen is displayed below:
Alt. Day of Month: #
(1-31)
Time HH:MM (0-23)
Enable: $(Y/N) OK? $(Y/N)
To edit the displayed values, press the
NO/0 key and ENTER key. Modify the values as desired.
Enter the Alternation Day of Month (1, 2, 3, 4….31 etc.) on which the pumps will be alternated.
Enter the Alternation Time in 24Hr format (range being 0:00-23:59).
Press
YES/7 key to enable Monthly alternation. Press the YES/7 key again to confirm the selection.
If 29,30 or 31 is entered as the day, the sequence will automatically alternate on the last day of the month.
Note:
In case Timed Auto Alt is in enabled state and Scheduled Auto Alt also gets enabled, Timed Auto Alt will get
disabled and a warning message “Timed Alteration will be disabled” will be displayed on the screen. Press
CLEAR key to go back to the ALTERNATION menu.
Installation