TECHNOFORCE Installation, Operation, and Maintenance

26

Installation

4.10.18 Communication menu

Paths: Status Screens / Set up(3) / System(3) / Communication(10)

See the following table for all

COMMUNICATION menu items.

Communication Menu Items

Menu Item

Variable

Default Range Field

Value

SELECTION SELECTION: #

0

1-3

Select the software protocol to drive the communications

on the optional RS-485 port. 1 = BACnet,

2 = JC Metasys, 3 = MODBUS, 0 = EXIT

4.10.19 BACnet MS/TP

The BACnet MS/TP screen is displayed below:
BACnet MS/TP
38400, 8, 1, 0, N
MAC: ### Inst= #######
AI Ovrd: $OK: $(Y/N)
The first line confirms setup for the

BACnet protocol. The second line defines the 38400 bps baud rate, 8 bit

data packets, 1 stop bit, 0 start bit and no parity. The third line requires user input. Obtain the node number from

the manufacturer that supplied the device that will communicate with the TechnoForce Controller.
See following table for all

BACNET MS/TP menu items.

BACnet MS/TP Menu Items

Menu Item

Variable

Default Range Field

Value

BACNET

Baud: #####

38400

9600,

MSTP

The baud rate is user adjustable parameter

19200,

38400

MAC: ###

2

1-255

The MAC address or node number should be supplied

by the BMS.

Inst: ###

100

0-9999

Unique instance numbers should be assigned for every

device on a BACnet network.

AI Ovrd: $

Select “Y” to override analog inputs through the

N

Y/N

communications port.

4.10.20 JC Metasys N2

The

JC Metasys N2 screen is displayed below:

JC Metasys N2
9600, 8, 1, 1, N, VND
Node: # AI Ovrd: $
OK: $(Y/N)
The first line confirms setup for the Johnson Controls

N2 protocol. The second line defines the 9600 bps baud

rate, 8 bit data packets, 1 stop bit, 1 start bit and no parity. The third line requires user input. Obtain the node

number from the manufacturer that supplied the device that will communicate with the TechnoForce Controller.