Bell & Gossett 210668B Z-4M User Manual

Bell & gossett, Zonetrol ii, Mcdonnell & miller zonesmart

background image

NOTICE: This instruction manual is a supplement to, not a

contact the point of purchase or download the necessary

manuals at www.bellgossett.com.

DESCRIPTION

The outdoor reset modules are integrated into the

McDonnell & Miller ZoneSmart or Bell & Gossett ZoneTrol II

zone controllers. By monitoring outdoor temperature and

indexing the system supply water to the varying heatloss of

the building, the reset controllers minimize fuel consumption

while maximizing occupant comfort.
The

Boiler Reset Control is designed to control a single

stage, non modulating heat source in order to provide outdoor

reset.
The

Mix Reset Control is designed to control the supply water

temperature to a hydronic system in order to provide outdoor

reset or setpoint operation. The control uses a variable speed

injection pump to regulate the supply water temperature, while

protecting the boiler against flue gas condensation.

Bell & Gossett

®

ZoneTrol II

Models Z-4B, Z-4M, Z-6B, Z-6M,

ZV-4B, ZV-4M, ZV-6B, ZV-6M

McDonnell & Miller ZoneSmart

Models ZS-4B, ZS-4M, ZS-6B, ZS-6M,

ZSV-4B, ZSV-4M, ZSV-6B, ZSV-6M

SAFETY

INSTRUCTION

This safety alert symbol will be used in this manual and on the

unit safety instructions decal to draw attention to safety related

instructions. When used, the safety alert symbol means

ATTEN-

TION! BECOME ALERT! YOUR SAFETY IS INVOLVED!

FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT

IN A SAFETY HAZARD.

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

Sensors Included
The Outdoor Temperature Sensor includes a

10 kΩ thermistor which provides an accurate

measurement of the outdoor temperature. The

sensor is protected by a white U.V. resistant

PVC plastic enclosure.

The Water Temperature Sensors have a zinc

sleeve for fast response and a wide operating

range. The sensors are supplied with 10 inches

(250mm) of two conductor wire.

SENSOR INSTALLATION INSTRUCTIONS

Outdoor Air Temperature Sensor
• Remove the screw and pull the front cover off the sensor

enclosure.

• The sensor can either be mounted directly onto a wall or a

2" x 4" electrical box.

• When the sensor is wall mounted, the wiring should enter

through the back or bottom of the enclosure. Do not mount

the sensor with the conduit knockout facing upwards as

water could enter the enclosure and damage the sensor.

• In order to prevent heat transmitted through the wall from

affecting the sensor reading, it may be necessary to install

an insulating barrier behind the enclosure.

• The sensor should be mounted on a wall which best repre-

sents the heat load on the building (a northern wall for most

buildings and a southern facing wall for buildings with large

south facing glass areas). The sensor should not be

exposed to heat sources such as ventilation or window

openings.