2 conformance statement, Product description, Bacnet standardized device profile (annex l) – Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual
Page 64: Segmentation capability, Standard object types supported

TECHNOFORCE Installation, Operation, and Maintenance
58
Appendix
7.2 Conformance Statement
BACnet Protocol Implementation
Conformance Statement
Date: 10/19/2010
Vendor Name: Xylem
Product Name:
TechnoForce Pump Controller
Product Model Number: N/A
Applications Software Version:
1.16 or above
Firmware Revision: N/A
BACnet Protocol Revision: 4.0
Product Description
The TechnoForce Pump Controller is a variable speed pumping system for water booster systems. It operates
either as a stand-alone controller or as part of a building-wide integrated system. The BACnet communication
interface will provide communication between the TechnoForce pump controller and the BACnet system residing
on EIA-485 media.
BACnet STandardized Device Profile (Annex L)
❑
BACnet Operator Workstation (B-OWS)
❑
BACnet Building Controller (B-BC)
❑
BACnet Advanced Application Controller (B-AAC)
❑
BACnet Application Specific Controller (B-ASC)
❑
BACnet Smart Sensor (B-SS)
❑
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K)
DS-RP-B
DM-TS-B
DM-DCC-B
DS-WP-B
DM-DDB-B
DM-DOB-B
Segmentation Capability
❑
Able to transmit segmented messages
Window Size
N/A
❑
Able to receive segmented messages
Window Size
N/A
Standard Object Types Supported
Analog input
Dynamically creatable:
No
Dynamically deletable:
No
Optional properties supported:
None
Writable properties:
Present Value
Conditionally writable
Out Of Service
Proprietary properties:
None
Property range restrictions:
None
✓