TECHNOFORCE Installation, Operation, and Maintenance
21
▲
▲
Note:
1. Use the (▲) and (▼) keys to select the appropriate resolution values
2. Use the Next/( ) key and Prev/( ) key to select the desired sign(+ or -) for
VALUE and OFFSET
variables
4.10.5 Exercise menu
Paths: Status Screens / Set up(3) / System(3) / Exercise(3)
See the following table for all
EXERCISE menu items.
Exercise Menu Items
Menu Item
Variable
Default Range Field
Value
EXERCISE
Period : #Hrs
0
0-999
Amount of time between automatic exercising of the
pumps, in seconds. A value of 0 disables pump exercising
Duration : ###s
0
0-999
Amount of time pumps will be exercised, all pumps
which have not run in the last period will be exercised
simultaneously
Pump exercising will ensure that no pumps go for long periods of time without running. Note that automatic
alternation can also provide this functionality. Pump exercising will only occur when the system is started and in
automatic operation. All pumps which need exercising will exercise on startup.
4.10.6 Alternation menu
Paths: Status Screens / Set up(3) / System(3) / Alternation(4)
The following
ALTERNATION menu options are available:
4.10.7 Timed auto alternation
See the following table for
TIMED AUTO ALTERNATION menu items.
Timed Auto Alternation Menu Items
Menu Item
Variable
Default Range Field
Value
Timed Auto
Period: #Hrs
168
0-999
Alt
Time between pump alternations when using “Timed
Auto Alternation”, in hours. A value of 0 will disable
this function
Duration: ###s
10
0-99
Amount of time that the running pumps will remain on
during alternation, in seconds
4.10.8 Scheduled auto alternation menu
See the following table for
SCHEDULED AUTO ALTERNATION menu items.
Scheduled Auto Alternation Menu Items
Menu Item
Variable
Default Range Field
Value
Scheduled
Scheduled Alt:
0
0-3
Auto Alt
Pump alternates based on the “Period” selected -
Daily: alternates daily based on the “Time”;
Weekly: alternates weekly based on the “Day” and
“Time”;
Monthly: alternates monthly based on the “Day” and
“Time”.
Note: At any time, only one of the 3 period based variables can be enabled.