TECHNOFORCE Installation, Operation, and Maintenance

36

Installation

4.10.44 High suction pressure

Paths: Status Screens / Set up(3) / AlrmEvt(5) / High Suction(5)

The High Suction Pressure menu is displayed below:
High Suct. Press: ##
High Suct Pr Tm: ##s Alarm: $
Alarm: $ Source: $$(AI/DI)
Reset Press: ## OK: $ (Y/N)
See following table for all

HIGH SUCTION PRESSURE menu items.

High Suction Pressure Menu Items

Menu Item

Variable

Default Range Field

Value

High

High Suct Press: ###

75

0-999

Suction

The pressure above which an alarm or event

Pressure

will be set for analog input method, in PSI.

High Suct Pr Tm: ###s

0

0-999

The proof timer prior to setting an alarm or event, in

seconds. A value of 0 disables this alarm.

Reset PSI: ###

67

0-999

The controller will automatically reset when the

suction pressure falls below the “Reset PSI”. Used for

analog input method only.

Alarm: $

N

Y/N

Set this value to “Y” to consider high suction pressure

an alarm, or set it to “N” to consider it an event.

Source:

$$

Select the desired value depending on the source. Use

AI

AI/DI

the (▲) Up and (▼) Down arrow keys to change the

source value

4.10.45 No flow shut down

Paths: Status Screens / Set up(3) / AlrmEvt(5) / NFSD(6)

The

No Flow Shut Down menu is displayed below:

NFSD Tst Pr Tmr ###s
Min Spd . Pr Tmr ##s
Restart PSI Drop ##
Min Run ##m OK $(Y/N)