TECHNOFORCE Installation, Operation, and Maintenance

37

See following table for all

NO FLOW SHUT DOWN menu items.

No Flow Shut Down Menu Items

Menu Item

Variable

Default Range Field

Value

No Flow

NFSD Tst Pr. Tmr: #s

10

0-999

Shut Down

The No Flow Shut Down test proof timer is the amount

of time, in seconds, the controller will run the system

while the PV is greater then SP.

A value of 0 will disable this alarm.

Min Spd Pr. Tmr #s

30

0-999

The Minimum Speed Proof Timer is the amount of time,

in seconds, the system will run at minimum speed before

shutting off.

Restart PSI Drop ##

10

0-999

The Restart PSI Drop is the value the PV variable needs

to be less then the SP in order to restart the system.

Min Run: ##m

1

0-999

Minimum Run is the minimum amount of time, in

minutes, that the system will run once it shuts down from

a no flow condition and restarts.

4.10.46 Low level

Paths: Status Screens / Set up(3) / AlrmEvt(5) / LowLevel(7)
The Low Level menu is displayed below:
Low Level Time: ###s
Stop Pumps?: $(Y/N)
Auto Reset?: $(Y/N)
OK? $ (Y/N)
See following table for all

LOW LEVEL menu items.

Low level Menu Items

Menu Item

Variable

Default Range Field

Value

Low Level

Low Level Time: ###s

0

0-999

The proof time, in seconds prior to setting a low level

EVENT, see section 4.10.17 to set up the low level

digital input. A value of 0 in Low Level Time variable

disables the Low Level function.

Stop Pumps?: $(Y/N)

N

Y/N

Select “Y” to allow pumps in this event to be

automatically stopped.

Auto Reset?: $(Y/N)

N

Y/N

Select “Y” to allow this event to be automatically reset.