TECHNOFORCE Installation, Operation, and Maintenance

32

Installation

4.10.34 LED test

Paths: Status Screens / Set up(3) / Test(4) / LED(5)
The LED test screen is displayed below:
LED Test
*** SOLID ***
*** OFF ***
*** FLASHING ***
All of the LED’s on the keypad will turn on, off, and then flash. The current status will be displayed on the

screen. The LED test is self terminating.

4.10.35 Key test

Paths: Status Screens / Set up(3) / Test(4) / Key(6)
The

KEY test screen is displayed below:

Key Test
Press a key to test
Press clear to exit
Press any key except for the

CLEAR key, and the display will confirm that the key is working by displaying the

key name. Press

CLEAR key to exit.

4.10.36 Display test

Paths: Status Screens / Set up(3) / Test(4) / Display(7)
The

DISPLAY test screen is shown below:

Press Clear To Exit
< 1 2 3 4 5 6 7 8 9
< 1 2 3 4 5 6 7 8 9
< 1 2 3 4 5 6 7 8 9
The display will show all black characters. Press

CLEAR key to exit the test.

4.10.37 Communication test

Paths: Status Screens / Set up(3) / Test(4) / Comm(8)

The

COMMUNICATION test screen is shown below:

Communication Test
Read: ####
Write: ####
Press Clear to Exit
If the controller is communicating properly with the building automation system, both numbers will continue

increasing in value. For Modbus protocol, the read and write numbers should be equal and increasing with every

poll. For BACnet, both numbers should be increasing, but they will not be equal. The write value will increase

even when not connected.
For the JC Metasys N2 protocol, both numbers should be increasing but may not be equal. If both numbers are

not increasing in value, the controller is not communicating properly. Check the wiring at the terminal blocks. See

section 4.10.18 for more information on communications setup. Press

CLEAR to exit this test.

4.10.38 VFD comm

Paths: Status Screens / Set up(3) / Test(4) / VFD Comm(9)
The

VFDCOMMUNICATION test screen is shown below:

VFD Comm Test
VFD Number: # (Same as Pump number)
Press Clear To Exit