The attached pages are a revision of sections 2.3.3, 2.3.4, and 2.3.5 of the Technologic 1100 Series Pump

Controller Instruction Manual (B&G Part #S11865). Replace these sections (of the manual) in entirety with

the attached.

Packaged Systems Group

Menu

Default

Allowable

Item # System Setup Display

Value

Range

Field Value

0

1)

User Password

0

0-65529

Password for entering User Setup and

password protected Service Test menu.

0

2)

Factory Setup Counter

1

1-10

# of times factory setup menu was performed.

The factory menu can not be accessed

without authorization from the factory.

0

3)

Horizontal Scroll Rate

3

1-10

Horizontal scroll rate in 100 milli-second units.

0

4)

Stage Stable

60

6-600

Staging stabilization time in seconds.

0

5)

Destage Proof

30

3-180

Destage proof time in seconds.

0

6)

AFD Minimum %

30

0-30

AFD minimum % speed.

0

7)

AFD Maximum %

100

0-100

AFD maximum % speed.

0

8)

AFD 1 Fail Time

20

5-999

Proof time for AFD 1 failure time in seconds.

0

9)

AFD 2 Fail Time

20

5-999

Proof time for AFD 2 failure in seconds.

10)

Destage %

85

0-99

Enter the percent of the stabilize pump

speed to be used as a destage point.

11)

Min. Destage %

0

0-100

Enter minimum % speed for staged

pumps to operate.

12)

Forced Dstg Tmr

0

0-999

Proof time prior to forced destaging of the

lag pump when min. speed (Min. Destage %)

of staged pumps is satisfied.

2.3.3 Confirm the system setup values per the following

table. Use the UP or DOWN ARROW keys to move

through the menu. To change values press ENTER,

modify the value using the numeric key pad or UP and

DOWN ARROW keys, press ENTER to accept the

modification.