Bell & Gossett S11865A TECHNOLOGIC 1100 SERIES PUMP CONTROLLER User Manual
Bell & gossett, Technologic, 1100 series pump controller

INSTRUCTION MANUAL
S11865
Addendum
Revision A
Bell & Gossett
Bell & Gossett
TECHNOLOGIC
™
1100 SERIES
PUMP CONTROLLER
The attached pages are a revision of sections 2.3.3, 2.3.4, and 2.3.5 of the Technologic 1100 Series Pump
Controller Instruction Manual (B&G Part #S11865). Replace these sections (of the manual) in entirety with
the attached.
Packaged Systems Group
Menu
Default
Allowable
Item # System Setup Display
Value
Range
Field Value
0
1)
User Password
0
0-65529
Password for entering User Setup and
password protected Service Test menu.
0
2)
Factory Setup Counter
1
1-10
# of times factory setup menu was performed.
The factory menu can not be accessed
without authorization from the factory.
0
3)
Horizontal Scroll Rate
3
1-10
Horizontal scroll rate in 100 milli-second units.
0
4)
Stage Stable
60
6-600
Staging stabilization time in seconds.
0
5)
Destage Proof
30
3-180
Destage proof time in seconds.
0
6)
AFD Minimum %
30
0-30
AFD minimum % speed.
0
7)
AFD Maximum %
100
0-100
AFD maximum % speed.
0
8)
AFD 1 Fail Time
20
5-999
Proof time for AFD 1 failure time in seconds.
0
9)
AFD 2 Fail Time
20
5-999
Proof time for AFD 2 failure in seconds.
10)
Destage %
85
0-99
Enter the percent of the stabilize pump
speed to be used as a destage point.
11)
Min. Destage %
0
0-100
Enter minimum % speed for staged
pumps to operate.
12)
Forced Dstg Tmr
0
0-999
Proof time prior to forced destaging of the
lag pump when min. speed (Min. Destage %)
of staged pumps is satisfied.
2.3.3 Confirm the system setup values per the following
table. Use the UP or DOWN ARROW keys to move
through the menu. To change values press ENTER,
modify the value using the numeric key pad or UP and
DOWN ARROW keys, press ENTER to accept the
modification.