TECHNOFORCE Installation, Operation, and Maintenance
52
Maintenance
6.14.8 Totalized value
Paths: Status Screens / Log(5) / Data Log(3) / Totalized Value(2)
The display now shows:
Total KWHr ###
Total Flow ###KGal
The total accumulated kilowatt hours and Flow is displayed as the Totalized Value
6.14.9 Operation
Paths: Status Screens / Log(5) / Operation(4)
The display now shows:
1=Op Mode Changes
2=Power Cycles
3=Events
NEXT/( ) key to go to the next screen. The display now shows:
4 = VFD
5 = EXERCISE
6 = Set Point
ENTER key. A detailed
description of each sub-menu appears.
6.14.10 Operation mode changes
Paths: Status Screens / Log(5) / Operation(4) / Op Mode Changes(1)
The display now shows:
MMDD HHMM Manual/Auto
MMDD HHMM Manual/Auto
MMDD HHMM Manual/Auto
MMDD HHMM Manual/Auto
Every time the
AUTO/ MANUAL key is pressed, the event will be logged by showing the state of operation
mode. The forty most recent operation mode changes will be stored. The date is displayed in MMDD format
and the time in 24 hour HHMM format. The most recent event will be shown first.
Press
NEXT/( ) and PREV/( ) view more log events. Press CLEAR to exit.
6.14.11 Power cycles
Paths: Status Screens / Log(5) / Operation(4) / Power Cycles(2)
The display now shows:
MMDD HHMM Power Up/Down
MMDD HHMM Power Up/Down
MMDD HHMM Power Up/Down
MMDD HHMM Power Up/Down
Each time the controller is powered up or down, the event will be logged. “Power Up” will be shown if powered
up, and “Power Down” will be shown if powered down. The forty most recent logs will be stored. The date is
displayed in MMDD format and the time in 24 hour HHMM format. The most recent event will be shown first.
Press
NEXT/( ) and PREV/( ) view more log events. Press CLEAR to exit.
▲
▲
▲
▲
▲