Appendix, 1 valid i/o codes – Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual

Page 63

background image

TECHNOFORCE Installation, Operation, and Maintenance

57

Appendix

7. Appendix

7.1 Valid I/O Codes

Code

Function Description

I/O Type

Range

Equate to

the Signal

101

Pump 1 Status (On/Off)

DO

1/0

On/Off

102

Pump 2 Status (On/Off)

DO

1/0

On/Off

103

Pump 3 Status (On/Off)

DO

1/0

On/Off

104

Pump 4 Status (On/Off)

DO

1/0

On/Off

105

Pump 5 Status (On/Off)

DO

1/0

On/Off

106

Pump 6 Status (On/Off)

DO

1/0

On/Off

111

Pump 1 Failure

DO

1/0

On/Off

112

Pump 2 Failure

DO

1/0

On/Off

113

Pump 3 Failure

DO

1/0

On/Off

114

Pump 4 Failure

DO

1/0

On/Off

115

Pump 5 Failure

DO

1/0

On/Off

116

Pump 6 Failure

DO

1/0

On/Off

121

VFD 1 Failure

DO

1/0

On/Off

122

VFD 2 Failure

DO

1/0

On/Off

123

VFD 3 Failure

DO

1/0

On/Off

124

VFD 4 Failure

DO

1/0

On/Off

125

VFD 5 Failure

DO

1/0

On/Off

126

VFD 6 Failure

DO

1/0

On/Off

140

A-V Alarm Output

DO

1/0

On/Off

171

Low Suction Detected, W/ Proof Time

DI

1/0

On/Off

172

High Suction Detected, W/ Proof Time

DI

1/0

On/Off

173

High Level Alarm Detected,W/ Proof Time

DI

1/0

On/Off

174

Low Level Alarm Detected, W/ Proof Time

DI

1/0

On/Off

175

Push to Silence Switch Input

DI

1/0

On/Off

201

Speed Signal

AO

0-100

4 - 20 ma

202

System Flow Rate

AO

0-Span

4 - 20 ma

203

System KW

AO

0-Span

4 - 20 ma

204

System Pressure

AO

0-Span

4 - 20 ma

205

Suction Pressure

AO

0-Span

4 - 20 ma

211

Analog Input 1

AO

0-Span

4 - 20 ma

212

Analog Input 2

AO

0-Span

4 - 20 ma

213

Analog Input 3

AO

0-Span

4 - 20 ma

214

Analog Input 4

AO

0-Span

4 - 20 ma